모세관 열교환기를 이용한 냉각장치에 관한 연구
- Alternative Title
- A Study on a Cooling System with Capillary Tube as Heat Exchanger
- Abstract
- An experimental study was conducted to verify performance of an air conditioning system with additional evaporator in the system that is fabricated with capillary tubes. Due to the multi-function of the capillary tube in the system as expansion device and heat exchanger makes reduction of investment price and increment of effectiveness of the heat exchanger.
In this study, capillary tube number, inner diameter and length of the capillary tube are selected as experimental parameter. The experiments are peformed with variation of operation condition of the air conditioning system. Mass flow rate of refrigerant, pressure and temperature at various point in the system and power consumption of the compressor is measured with coriolis type mass flow meter, pressure transducer, t-type thermocouple and power meter, respectively.
As results, the Coeffciency of performance calculation result was that only 50 percent of each experimental condition was more than 1 Coeffciency of performance. and Most results of 6 capillary tube connected in parallel condition were more than 1 Coeffciency of performance.
In case of 10 capillary tube, the Coeffciency of performance Significantly decreased unless the temperature of the cooling water was low.
It means that the more diameter and condensing temperature of the capillary tube is high, the more compressor operation rate and energy consumption and the less efficiency.
As a result, because capillary tube absorbs heat from environment, when temperature of the cooling water is low, capillary tube can drop the condenser temperature much more so that electronic power consumption can be minimized. If more research can be done on heat exchange through capillary tube, we can expect an more efficient energy-saving solution in the very future.
- Author(s)
- 이남훈
- Issued Date
- 2008
- Awarded Date
- 2008. 8
- Type
- Dissertation
- URI
- http://dcoll.jejunu.ac.kr/jsp/common/DcLoOrgPer.jsp?sItemId=000000004397
- Alternative Author(s)
- Lee, Nam Hun
- Affiliation
- 제주대학교 산업대학원
- Department
- 산업대학원 기계공학과
- Advisor
- 玄眀澤
- Table Of Contents
- 1. 서론 1
1.1 연구 배경 1
1.2 연구동향 4
2. 실험장치 및 실험방법 7
2.1 실험장치의 사이클 구성 7
2.2 실험장치 및 주요 요소기기 9
2.3 계측장치와 측정방법 14
2.4 이론해석 및 열전달 17
2.5 실험 조건 19
3. 실험 결과 및 고찰 21
3.1 모세관의 온도변화 21
3.1.1 응축온도 변화에 따른 모세관의 온도변화 21
3.1.2 모세관 개수에 따른 구간별 성능분포 22
3.1.3 냉매유량의 변화 23
3.2 시스템의 성능변화 37
3.2.1 압력변화 37
3.2.2 온도변화 37
3.3 시스템의 냉동성적계수 비교 45
3.3.1 시스템 소비전력 45
3.4 시스템의 성능계수 49
4. 결론 54
5. 참고 문헌 56
- Degree
- Master
- Publisher
- 제주대학교 산업대학원
- Citation
- 이남훈. (2008). 모세관 열교환기를 이용한 냉각장치에 관한 연구
-
Appears in Collections:
- Graduate School of Industry > Machanical Engineering
- Authorize & License
-
- Files in This Item:
-
Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.